All tables are based on the operation of the motor and controller in the same ambient temperature, 40° C (104° F) or less. Always be certain the correct thermal units are installed in the starter before operating the motor. Each thermal unit shall be installed such that its catalog number is visible. Figure 1 for complete thermal unit installation instructions. On melting alloy thermal units the ratchet wheel must engage the pawl assembly.
To select Type SB slow trip thermal units, the selection table for a standard Type B thermal unit may be used with the following modifications: For continuous rated motors having service factors of 1.15 to 1.25, select thermal units from the standard Type B table using 93% (102% for Class 8198) of the full load current shown on the motor nameplate and then substitute an SB for the B in the thermal unit type number.
Example: A motor with a full load current of 12 amps controlled by an 8536SCG3 would require B22 thermal units for standard trip applications and SB19.5 thermal units for slow trip applications. The SB is selected by multiplying 12 amps times 93% for 11.16 amps and using this value to select B19.5. Then add the S prefix to arrive at SB19.5.
For continuous rated motors having a service factor of 1.0, select thermal units in the same manner using 84% (93% for Class 8198) of full load current shown on the motor nameplate.
Note: SB thermal units are used on Size 0, 1, 2 and only some Size 3 applications. Check thermal unit tables for current ranges.
Controller
|
Thermal Unit Selection Table Number
|
||||||||
---|---|---|---|---|---|---|---|---|---|
Hand Reset Melting Alloy
|
Bimetallic
|
||||||||
Starter Type
|
Class
|
Type
|
Seriesa
|
Size
|
Standard
Trip (20) |
Quick Trip
(10) |
Slow Trip
(30) |
Non-
Compensated |
Compen-
sated |
Manual
Starters FHP |
2510
2512 8908 |
F
|
A
|
FHP
|
43h
|
...
|
...
|
...
|
...
|
Manual Starters
(Small Enclosure) |
2510
|
M, T
|
A
|
M–0
M–1 M–1P |
1
1 1 |
72
72 72 |
...
... ... |
...
... ... |
|
Manual
Starters (Large Enclosure) |
2510
2511 2512 8925 |
M, T
|
A
|
M–0
M–1 M–1P |
2
2 2 |
73
73 73 |
...
... ... |
...
... ... |
|
Manual
Loom Sw. |
2510
|
MBL, TBL
|
A
|
M–0
|
7
|
...
|
...
|
...
|
|
DC
Magnetic Starters |
7135
7136 7735 7736 |
C, D
|
...
|
1,2
|
65
|
...
|
...
|
...
|
|
E
|
...
|
3
|
9
|
...
|
...
|
...
|
...
|
||
F
|
...
|
4
|
10
|
...
|
...
|
...
|
...
|
||
G
|
...
|
5
|
12
|
...
|
...
|
...
|
...
|
||
AC
Magnetic Starters (Small Enclosure) |
8933
8998
8999 (Model 3 Control Center)
I-LINE®
and QMB
Motor Starter Centers |
A
(8536 only) |
B, C
|
00
|
17h
|
...
|
...
|
...
|
...
|
SA
|
A, B
|
00
|
13
|
...
|
...
|
...
|
|||
SB
|
A
|
0
|
13
|
74
|
8
|
33
|
|||
SC
|
A
|
1
|
13
|
74
|
8
|
33
|
|||
A
|
1P
|
41
|
...
|
...
|
...
|
||||
SD
|
A
|
2
|
56
|
75
|
62
|
70
|
|||
SE
|
A
|
3
|
18
|
76i
|
63
|
37g
|
|||
B
|
3
|
...
|
...
|
...
|
142
|
...
|
|||
SF
|
A
|
4
|
54
|
77i
|
...
|
11
|
29g
|
||
B
|
4
|
...
|
...
|
...
|
144
|
...
|
|||
SG
|
A
|
5
|
49
|
...
|
...
|
38
|
46
|
||
Bl
|
5
|
59
|
83
|
...
|
23
|
42
|
|||
SH
|
A, B
|
6
|
21
|
...
|
...
|
39
|
47
|
||
8998
8999 (Model 4 Control Center) |
SC
|
A
|
1 Fusible
|
66
|
74
|
...
|
64
|
33
|
|
1 Circuit Breaker
|
15
|
74
|
...
|
||||||
SD
|
A
|
2 Fusible
|
67
|
75
|
...
|
57
|
70
|
||
2 Circuit Breaker
|
58f
|
75
|
...
|
||||||
SE
|
A
|
3 Small Enclosure
|
16
|
76i
|
51
|
37g
|
|||
3 Large Enclosure
|
68f
|
76i
|
|
|
|||||
B
|
3
|
...
|
...
|
...
|
141
|
...
|
|||
SF
|
A
|
4
|
61
|
77i
|
...
|
35
|
29f
|
||
B
|
4
|
...
|
...
|
...
|
143
|
...
|
|||
SG
|
A
|
5
|
24
|
...
|
...
|
52
|
46
|
||
SH
|
A
|
6
|
20
|
...
|
...
|
48
|
47
|
||
8998
(Model 5 and Model 6 MCCs) |
SCk
|
A
|
1
|
109
|
...
|
...
|
...
|
97
|
|
1 COMPAC 6
|
104
|
...
|
...
|
...
|
...
|
||||
SDk
|
A
|
2
|
110
|
...
|
...
|
...
|
98
|
||
SEk
|
A
|
3
|
111
|
...
|
...
|
...
|
99
|
||
SFk
|
A
|
4
|
112
|
...
|
...
|
...
|
100
|
||
SGk
|
A
|
5
|
113
|
...
|
...
|
...
|
101
|
||
Bl
|
5 CT
|
103
|
...
|
...
|
...
|
...
|
|||
SHk
|
A
|
6
|
114
|
...
|
...
|
...
|
102
|
||
8911
|
DPSG
|
A
|
20–30 A
|
135
|
...
|
...
|
...
|
...
|
|
40 A
|
145
|
...
|
...
|
...
|
...
|
||||
50 A
|
146
|
...
|
...
|
...
|
...
|
||||
60–90 A
|
149
|
...
|
...
|
...
|
...
|
Controller
|
Thermal Unit Selection Table Number
|
||||||||
---|---|---|---|---|---|---|---|---|---|
Hand Reset Melting Alloy
|
Bimetallic
|
||||||||
Starter Type
|
Class
|
Type
|
Seriesa
|
Size
|
Standard
Trip |
Quick Trip
(10) |
Slow Trip
(30) |
Non-
Compensated |
Compensated
|
AC
Magnetic Starters (Large Enclosure) |
8198
|
G, S
|
...
|
...
|
5
|
...
|
...
|
6
|
|
8536
(Starter Used in Multi-Motor Panel) |
A
(8536 only) |
B, C
|
00
|
14h
|
...
|
...
|
...
|
...
|
|
SA
|
A, B
|
00
|
53
|
...
|
55
|
25
|
|||
SB, NB
|
A
|
0
|
15
|
78
|
64
|
33
|
|||
SC, NC
|
A
|
1
|
15
|
78
|
64
|
33
|
|||
SD, ND
|
A
|
2
|
58
|
79
|
57
|
70
|
|||
SE, NE
|
A
|
3
|
16
|
80i
|
51
|
37g
|
|||
B
|
3
|
...
|
...
|
...
|
141
|
...
|
|||
SF, NF
|
A
|
4
|
61
|
81i
|
...
|
35
|
29g
|
||
B
|
4
|
...
|
...
|
...
|
143
|
...
|
|||
SG
|
A
|
5
|
24
|
...
|
...
|
52
|
46
|
||
Bl
|
5
|
59
|
83
|
...
|
23
|
42
|
|||
SH
|
A, B
|
6
|
20
|
...
|
48
|
47
|
|||
8810
8811 8812 |
CB, DB, SB, UB
|
A
|
0
|
15
|
78
|
64
|
33
|
||
CC, DC, SC, UC
|
A
|
1
|
15
|
78
|
64
|
33
|
|||
CD, DD, SD, UD
|
A
|
2
|
58
|
79
|
57
|
70
|
|||
CE, DE, SE, UE
|
A
|
3
|
16
|
80i
|
51
|
37g
|
|||
CF, DF, SF, UF
|
A
|
4
|
61
|
81i
|
...
|
35
|
29g
|
||
SE
|
B
|
3
|
...
|
...
|
...
|
141
|
...
|
||
SF
|
B
|
4
|
...
|
...
|
...
|
143
|
...
|
||
CG, DG, SG, UG
|
A
|
5
|
24
|
...
|
...
|
52
|
46
|
||
Bl
|
5
|
59
|
83
|
...
|
23
|
42
|
|||
CH, DH, SH, UH
|
A
|
6
|
20
|
...
|
48
|
47
|
|||
8940
WELL-GUARD®
Control |
WC, XC
|
A
|
1
|
13
|
78
|
...
|
...
|
33
|
|
WD, XD, MD, RD, VD
|
A
|
2
|
56
|
79
|
...
|
...
|
70
|
||
WE, XE, ME, RE, VE
|
A
|
3
|
18
|
80i
|
...
|
...
|
37
|
||
PF, WF, XF, MF, RF, VF, PE
|
A
|
4
|
54
|
81i
|
...
|
...
|
29
|
||
XSG, NSG, MG,RG, VGh
|
A
|
5
|
...
|
...
|
...
|
...
|
46
|
||
Bl
|
5
|
...
|
...
|
...
|
...
|
42
|
|||
XSH, VH
|
A
|
6
|
...
|
...
|
...
|
...
|
47
|
||
8911
|
DPSO
|
A
|
20–30 A
|
136
|
...
|
...
|
...
|
...
|
|
40 A
|
147
|
...
|
...
|
...
|
...
|
||||
50 A
|
148
|
...
|
...
|
...
|
...
|
||||
60–90 A
|
150
|
...
|
...
|
...
|
...
|
||||
AC
Magnetic Part- Winding |
8998
(Model 5 and Model 6 MCCs) |
SCk
|
A
|
1
|
127
|
...
|
...
|
...
|
121
|
SDk
|
A
|
2
|
128
|
...
|
...
|
...
|
122
|
||
SEk
|
A
|
3
|
129
|
...
|
...
|
...
|
123
|
||
SF
|
A
|
4
|
105
|
...
|
...
|
...
|
117
|
||
SG
|
A
|
5
|
115
|
...
|
...
|
...
|
118
|
||
Bl
|
5 CT
|
116
|
...
|
...
|
...
|
...
|
|||
Separately
Mounted Overload Relays |
9065
|
AF
|
B
|
4(133 A)
|
...
|
...
|
...
|
30
|
...
|
AG
|
A
|
5(266 A)
|
...
|
...
|
...
|
36
|
...
|
||
AR
|
A
|
1(25 A)
|
...
|
...
|
...
|
32
|
...
|
||
AT
|
A
|
2(45 A)
|
...
|
...
|
...
|
60
|
...
|
||
AU
|
...
|
3(86 A)
|
...
|
...
|
...
|
50
|
...
|
||
DA
|
A
|
1(25 A)
|
...
|
...
|
...
|
140g
|
...
|
||
GA
|
A
|
2(60 A)
|
...
|
...
|
...
|
139g
|
...
|
||
HA
|
A
|
3(100 A)
|
...
|
...
|
...
|
138g
|
...
|
||
JA
|
A
|
4(180 A)
|
...
|
...
|
...
|
137g
|
...
|
||
C
|
A
|
1(25 A)
|
44
|
82
|
...
|
...
|
|||
F
|
B
|
4(133 A)
|
19
|
85i
|
...
|
...
|
...
|
||
G
|
A
|
5(266 A)
|
22
|
...
|
...
|
...
|
...
|
||
MEO
|
A
|
(32 A)
|
86
|
...
|
...
|
...
|
...
|
||
S
|
A
|
1(26 A)
|
59
|
83
|
23
|
42
|
|||
2(45 A)
|
69
|
84
|
27
|
71
|
|||||
3(86 A)
|
34
|
...
|
...
|
...
|
...
|
||||
4(133 A)
|
28
|
...
|
...
|
...
|
...
|
||||
T
|
A
|
2(45 A)
|
31
|
...
|
...
|
...
|
|||
U
|
...
|
3(86 A)
|
40
|
...
|
...
|
...
|
...
|
4/1/04 |