Eutectic Alloy Overload Relay Heater
Elements
-
Type
J — CLASS 10
-
Type
P — CLASS 20 (Bul. 600 ONLY)
-
Type
W — CLASS 20
-
Type
WL — CLASS 30
Allen
Bradley Heater
Element Selection
Description
Overload
Relay Class Designation
United States
Industry Standards (NEMA Part ICS 2-222) designate an overload relay by a class
number indicating the maximum time in seconds at which it will trip when
carrying a current equal to 600 percent of its current rating.
A Class 10 overload relay will trip in 10 seconds or less at a current equal to
600 percent of its rating.
A Class 20 overload relay will trip in 20 seconds or less at a current equal to
600 percent of its rating.
A Class 30 overload relay will trip in 30 seconds or less at a current equal to
600 percent of its rating.
Allen-Bradley standard overload relay protection is provided using Type W heater
elements for the 500 Line. This provides Class 20 operation and is recommended
for General Applications.
Specific Applications may require Class 10 or Class 30 overload relays. Class 10
overload relays are often used with hermetic motors, submersible pumps, or
motors with short locked rotor time capability. Class 30 overload relays should
be used with motors driving high inertia loads, where additional accelerating
time is needed and the safe permissible locked rotor time of the motor is within
Class 30 performance requirements.
For applications requiring Class 30 protection, Type WL heater elements are
available. To order, use the applicable Type W selection table, follow the
heater element selection instructions and change the “W” in the
Heater Type Number to “WL”.
For applications requiring Class 10 overload relays, Type J elements are
available. See page Index
to Heater Element Selection Tables for Index to Heater Element Selection
Tables.
Heater
Element Selection
The “Full Load Amperes” listed
in the tables are to be used for heater element selection. For Type J and W
Heater Elements, the rating of the relay in amperes at +40 °C (+104 °F) is
115% of the “Full Load Amperes” listed for the “Heater Type Number”. For
Type WL Heater Elements, the rating is 120% of the “Full Load Amperes”
listed for the “Heater Type Number.”
Refer to the motor nameplate for the full load current, the service factor,
and/or the motor classification by application and temperature rise.
Use this motor nameplate information, the application rules, and the “Full
Load Amperes” listed in the proper table (see Index) to determine the
“Heater Type Number.”
The
following is for motors rated for Continuous Duty:
For motors with marked service factor of not less than 1.15, or motors with a
marked temperature rise not over +40 °C (+104 °F), apply application rules 1
through 3. Apply application rules 2 and 3 when the temperature difference does
not exceed +10 °C (+18 °F). When the temperature difference is greater, see
below.
1. The Same Temperature at the Controller and the Motor
— Select the “Heater Type Number” with the listed “Full Load Amperes”
nearest the full load value shown on the motor nameplate.
2. Higher Temperature at the Controller than at the Motor
— If the full load current value shown on the motor nameplate is between the
listed “Full Load Amperes”, select the “Heater Type Number” with the
higher value.
3. Lower Temperature at the Controller than at the Motor
— If the full load current value shown on the motor nameplate is between the
listed “Full Load Amperes”, select the “Heater Type Number” with the
lower value.
For motors with Marked Service Factor of less than 1.15, select the “Heater
Type Number” one rating smaller than determined by the rules in paragraphs 1,
2 and 3.
Motors rated for Intermittent Duty — Consult your local Allen-Bradley
distributor.
Heater Element Selection
Procedure — When Temperature at Controller is More Than ±10 °C (±18 °F)
Different Than Temperature At Motor
Ambient
Temperature Correction
The ambient temperature at the
motor and controller is the same in most applications. Under this condition, the
overload relay is designed to sense changes in ambient temperature and also
protect the motor over a range of temperatures.
Output that a motor can safely deliver varies with temperature. The motor can
deliver its full rated horsepower at an ambient temperature specified by the
motor manufacturers, normally +40 °C (+104 °F). At high temperatures (higher
than +40 °C) less than 100% of the normal rated current can be drawn from the
motor without shortening the insulation life. At lower temperatures (less than
+40 °C) more than 100% of the normal rated current could be drawn from the
motor without shortening the insulation life. Thus, there is an inverse
relationship between motor ambient temperature and motor output. In any motor,
allowable output decreases as the ambient temperature is raised and vice versa.
Heater Element Selection
Procedure — When Temperature at Controller is More Than ±10 °C (±18 °F)
Different Than Temperature At Motor, Continued
Ambient
Temperature Correction Curve
(See Performance Data, page Important 2)
When the temperature
difference between the motor and controller does not exceed +10 °C the heater
elements should be selected according to the directions given in the Heater
Element Selection, Overload
Relay Class Designation.
When the temperature difference is more than +10 °C an ambient temperature
correction factor should be used as part of the process for selecting heater
elements. The ambient temperature correction curve shown below shows the factor
by which heater selection rating changes with ambient temperature changes.
Heater Element Selection
Procedure
1. First find the
correction factor ratio (“C.F.R.”). This is the ratio of correction factor
of the motor ambient temperature (C.F.m) to the correction factor for the
controller ambient temperature (C.F.c). The formula for calculating the
correction factor ratio is:
Both
correction factors are selected from the curve for the type of heater element to
be used. The heater element selection tables are based on a +40 °C ambient
temperature. This means the correction factor for a +40 °C is 1.00. In other
words, there is no correction factor at +40 °C.
2. Next in this heater element selection process is to adjust
the motor nameplate full load current (FLC) by the C.F. Ratio. This readjusted
value of motor nameplate full load current (FLC) is the yardstick in selecting
the proper heater element.
3. The last step is to refer to the suggested heater element
table and pick the element whose rating for the given controller size is closest
to FLC.
Examples — To become familiar with this heater element selection
process, consider a few examples.
Example 1. Starter at Normal +40 °C Ambient — Motor Lower. 3-Phase,
AC, squirrel cage motor, 25 Hp, 460V, 60 Hz, 1800 rpm, FLC of 34 A, service
factor 1.15, Temperature at starter +40 °C, Temperature at motor +25 °C,
Type W heater elements will be used.
In Example 1, the motor is at a much cooler ambient temperature (+25 °C)
compared to the controller which is at the normal +40 °C. Because the motor is
normally rated for use at +40 °C, it will deliver a little more than its rated
horsepower. This means that a heater element with a higher than normal motor
nameplate full load current rating can be used.
Referring to the Type W ambient temperature correction curve on this page for a
motor at +25 °C ambient, the motor correction factor (C.F. motor) is shown to
be 108%. The correction factor for the starter ambient temperature is 100% since
it is at +40 °C. Thus,
Now, using this correction factor,
the readjusted full load current value can be determined by:
A Bulletin 512, Size 2, was
specified for this application. The directions for heater element selection
indicate that Table 153 should be used. The table shows that 36.7 A falls
between two values, 35.0 A (W66) and 38.0 A (W67). Because 38.0 A is closer to
the requirement, select the heater element W67.
Example 2. Starter at Normal +40 °C Ambient — Motor Higher. 3 Phase
AC, squirrel cage motor, 25 Hp, 460V, 60 Hz, 1800 rpm. FLC of 34 A, service
factor 1.15. Type W heater elements, Temperature at starter +40 °C,
Temperature at motor +55 °C.
This represents a situation where the motor ambient temperature is higher than
+40 °C. In this example, the motor is at +55 °C ambient temperature and the
controller is at +40 °C. When the motor is functioning in a warmer environment
than the controller it will not be able to deliver the normal horsepower. To
protect it from damage, it becomes necessary to downsize the heater element
compared to the same motor operating in a +40 °C ambient temperature. Referring
to the Type W ambient temperature correction curve, the correction factor would
be:
Having determined the correction
factor, the current rating to be used when selecting a heater element would be:
For Bulletin 512, Size 2, again
refer to Table 153. The value of 30.9 A falls between 30.0 A (W64) and 32.5 A
(W66). Since 30.0 is closer to 30.9 specify the W64 heater element.
Example 3: Starter Lower than +40 °C — Motor Higher. 3-Phase, AC,
squirrel cage motor, 25 Hp, 460V, 60 Hz, 1800 rpm. FLC of 34 A, service factor
1.15. Type W heater elements, Temperature at starter +25 °C, Temperature at
motor +55 °C.
Next, consider a case where both the controller and the motor are at ambient
temperatures other than +40 °C. In Example 3 the temperature of the controller
is +25 °C ambient (cooler) while the temperature of the motor is +55 °C
ambient (warmer). As stated earlier, a motor running in a warmer environment
will deliver less than its normal horsepower. This requires downsizing the
heater element rating. The controller in this case is in a cooler environment
which prevents the heater element from heating up as much as in a +40 °C
ambient temperature. This also requires downsizing the heater element rating to
provide adequate protection. Thus, the net effect of a warmer motor and a cooler
controller is to further downsize the heater element. Using the Type W
temperature correction curve, the correction factor in this case is:
The readjusted value of current FLC
for this example is:
Table 153 shows that this value
falls between 28.0 A (W63) and 30.0 A (W64). Because 28.0 A is closer to the
requirement, select the heater element W63.
Heater Element Selection
Procedure, Continued
Example 4: Starter Above +40 °C
— Motor Lower. 3-Phase, AC, squirrel cage motor, 25 Hp, 460V, 60 Hz, 1800
rpm. FLC of 34 A, service factor 1.15. Type W heater elements, Temperature at
starter +65 °C, Temperature at motor +35 °C.
Now, consider the effect of a controller in a warmer environment and a motor in
a cooler environment. In Example 4, the controller is at +65 °C ambient
(warmer) and the motor at +35 °C ambient (cooler). As mentioned earlier, a
motor at a cooler temperature can deliver more than its normal horsepower. The
controller when in a warmer environment will heat up faster causing the eutectic
alloy to melt before the normal overload condition. This requires upsizing the
heater element rating. Referring to the Type W ambient temperature correction
curve (Overload
Relay Class Designation), the correction factor in this case is:
This correction factor allows a
heater element with current rating of:
Referring to Table 153, this value
of 41.4 A falls between 40.5 A (W68) and 43.5 A (W69). Because 40.5 A is closer
to the requirement, select heater element W68.
Example 5: Starter Above +40 °C — Motor Above. 3-Phase, AC, squirrel
cage motor, 25 Hp, 460V, 60 Hz, 1800 rpm. FLC of 35 A, service factor 1.15. Type
W heater elements, Temperature at starter +45 °C, Temperature at motor +60
°C.
Next, take an example where both the controller and the motor are both warmer
than +40 °C ambient temperature but their ambient temperatures are different.
For instance, the controller could be at +45 °C ambient and the motor is at +60
°C ambient. Since the difference in their ambient temperatures is greater than
+10 °C an ambient temperature correction must be made. In Example 5 the
correction factor is given by:
This means that the rating of the
heater element should be 90% of the normal nameplate motor full load current or:
For Bulletin 512, Size 2
controller, Table 153 shows this rating to fall between 30.0 A (W64) and 32.5 A
(W65). Because 32.5 A is closer, select heater element W65. Note here that the
net effect has been to downsize the heater element rating compared to a normal
+40 °C ambient operation.
Note: The heater element selection tables are designed to accommodate
motor service factors of 1.15 or greater, as given in all the preceding
examples. If the service factor had been less than 1.15 (for example, S.F. =
1.0) a heater element one rating smaller than selected in each example would
have been the correct choice. This would provide protection at 10% lower current
levels.
Time — Current
Characteristics at +40 °C (+104 °F) (See Performance Data, page Important-2