Cutler Hammer Freedom Series Overload Relay Heater Elements for Motor Protection
Cutler Hammer Freedom Series overload relays have load lugs built into the overload relay to allow load wiring before heater pack installation. Heater packs H2001B to H2017B and H2101B to H2117B are to be used only with series B relays.
Heater packs - Class 10 and 20
For Use w/ Series "B" OL Relays (Built-In Load Lugs)
Standard Trip - Class 20
Overload
Relay Size
Motor Full Load Ampere Rating
Catalog Number
(Includes 3 Heater Packs)
Dial Position
A
B
C
D
For Use W/ NEMA Sizes 00-0 Series C, NEMA Sizes 1-2 Series B;
I.E.C. Sizes A-F Series C, I.E.C. Sizes G-K Series B
32 A or 75 A .254
.375
.560
.814
1.20
1.79
2.15
3.23
4.55
6.75
9.14
14.0
18.7
23.5.306
.452
.676
.983
1.45
2.16
2.60
3.90
5.50
8.17
10.8
16.9
22.7
28.5.359
.530
.791
1.15
1.71
2.53
3.04
4.56
6.45
9.58
12.4
19.9
26.7
33.5.411
.607
.907
1.32
1.96
2.90
3.49
5.23
7.40
11.0
14.0
22.8
30.7
38.5H2001B-3
H2002B-3
H2003B-3
H2004B-3
H2005B-3
H2006B-3
H2007B-3
H2008B-3
H2009B-3
H2010B-3
H2011B-3
H2012B-3
H2013B-3
H2014B-3For use with NEMA size 2, I.E.C. Sizes G-K only - Series B 75 A 29.0
39.6
53.934.0
45.5
60.939.1
51.5
67.944.1
57.4
74.9H2015B-3
H2016B-3
H2017B-3For use with NEMA sizes 3-4 I.E.C Sizes L-N only - Series A 105 A
or
144 A18.0
24.6
33.5
45.7
62.2
84.7
106.020.2
27.6
37.5
51.2
69.7
95.0
118.022.3
30.5
41.5
56.7
77.1
105.0
131.024.5
33.4
45.6
62.1
84.6
115.0
144.0H2018-3
H2019-3
H2020-3
H2021-3
H2022-3
H2023-3
H2024-3For Use with Size 5 Starters Only - Series B 32 A1 49
72
107
129
19459
87
130
156
23469
103
152
182
27479
118
174
209
-H2004B-3
H2005B-3
H2006B-3
H2007B-3
H2008B-3For use with size 6 starters only - Series B 32 A1 144
215
258
388174
259
312
468205
304
365
547235
348
419
-H2005B-3
H2006B-3
H2007B-3
H2008B-3For use with size 7 starters only - Series B 32 A1 163
240
358
430
646197
290
432
520
780230
342
506
608
912264
392
580
698
-H2004B-3
H2005B-3
H2006B-3
H2007B-3
H2008B-3For use with size 8 starters only - Series B 32 A1 244
360
537
645
969295
435
648
780
1170345
513
759
912
1368396
588
870
1047
-H2004B-3
H2005B-3
H2006B-3
H2007B-3
H2008B-3
1Sizes 5-8 use the 32 ampere overload relay with current transformers.
Fast Trip - Class 10
Overload Relay Size | Motor Full Load Ampere Rating | Catalog Number | |||
Dial Position | |||||
A | B | C | D | ||
For Use with NEMA sizes 00-0 Series C, NEMA Sizes 1-2 Series B; I.E.C. Sizes A-F Series C, I.E.C. Sizes G-K Series B | |||||
32
A or 75 A |
.260 .384 .570 .846 1.28 1.92 2.30 3.38 4.96 7.07 9.60 14.4 18.7 23.5 |
.313 .464 .688 1.02 1.55 2.33 2.79 4.10 6.03 8.58 11.2 17.5 21.8 27.3 |
.367 .543 .806 1.20 1.83 2.74 3.28 4.82 7.09 10.1 12.8 20.7 25.0 31.0 |
.420 .623 .924 1.37 2.10 3.15 3.77 5.54 8.16 11.6 14.4 23.8 28.1 34.8 |
H2101B-3 H2102B-3 H2103B-3 H2104B-3 H2105B-3 H2106B-3 H2107B-3 H2108B-3 H2109B-3 H2110B-3 H2111B-3 H2112B-3 H2113B-3 H2114B-3 |
For use with NEMA Size 2, I.E.C. Sizes G-K Only - Series B | |||||
75 A | 28.3 36.6 53.8 |
32.6 42.3 60.8 |
37.0 48.1 67.9 |
41.3 53.8 74.9 |
H2115B-3B H2116B-3B H2117B-3B |
For use with Size 5 Starters Only - Series B | |||||
32 A1 | 51 77 115 138 203 |
61 93 140 167 246 |
72 110 164 197 289 |
82 126 189 226 - |
H2104B-3 H2105B-3 H2106B-3 H2107B-3 H2108B-3 |
For use with Size 6 Starters Only - Series B | |||||
32 A1 | 154 230 276 406 |
186 280 335 492 |
220 329 394 578 |
252 378 452 - |
H2105B-3 H2106B-3 H2107B-3 H2108B-3 |
For use with Size 7 Starters Only - Series B | |||||
32 A1 | 169 256 384 460 676 |
204 310 466 558 820 |
240 366 543 656 - |
274 420 630 754 - |
H2104B-3 H2105B-3 H2106B-3 H2107B-3 H2108B-3 |
For use with Size 7 Starters only - Series B | |||||
32 A1 | 254 384 576 690 1014 |
306 465 699 837 1230 |
360 549 822 984 - |
411 630 945 1131 - |
H2104B-3 H2105B-3 H2106B-3 H2107B-3 H2108B-3 |
1Sizes 5-8 use the 32 ampere overload relay with current transformers.
Starters W/ Series "B" Overload Relays
The series of a starter is the last digit of the listed Cat. No. Example: AN16DN0AB | NEMA - AN Type | I.E.C. - AE Type | ||
Size | Series | Size | Series | |
00-0 1-2 5 to 8 |
C B B |
A
to F G to K |
C B |
Pioneer Breaker & Control Supply is not an authorized distributor of Cutler Hammer products and Cutler Hammer trademarks are owned by Cutler Hammer Inc